Radiator BTU calculator
The heat a room needs, in watts and BTU/h: see the room with its cold walls, and the radiator drawn at the length to fit, on a boiler or a heat pump.
Double panel, 600 mm high, to scale
Job sheet
Radiator BTU calculator- Heat needed
- 5,960 BTU/h
- 1,750 W, 1.75 kW
- Radiator, boiler (ΔT50)
- 1,750 W
- its output at ΔT50, as sold
- Radiator, heat pump (ΔT30)
- 3,390 W
- its output at ΔT50: it gives about 51% of it at ΔT30
- Length on a boiler
- 1.3 m
- double panel, 600 mm high
- Length on a heat pump
- 2.4 m
- double panel, 600 mm high
How it works
The heat a room needs is what it loses on a cold day, through its walls, windows, floor and ceiling, and in draughts. This rule of thumb works it out from the room’s volume.
- Volume: length × width × height, in m³.
- Watts: volume × watts a m³ for the room (living room 52, bedroom 40, kitchen 40, bathroom 58, hall 45), × the insulation (poor × 1.3, average × 1, good × 0.7), + 15% for each outside wall past the first.
- BTU/h: watts × 3.412.
- On a heat pump: radiators are rated at ΔT50; at ΔT30 they give about 51%, so divide the watts by 0.51.
A worked example
A 4 × 3.5 m living room, 2.4 m high: 33.6 m³ × 52 W = 1,750 W, or 5,960 BTU/h. On a boiler, pick a radiator rated about 1,750 W at ΔT50; on a heat pump, about 3,390 W at ΔT50.
The figures are a first look for one room. A whole-house heat loss calculation (EN 12831) sizes the boiler or heat pump and every radiator properly.
Questions
How many BTUs do I need to heat a room?
Roughly the room’s volume in m³ × 52 W for a living room (40 for a bedroom) in an averagely insulated home, × 3.412 for BTU/h. A 4 × 3.5 m living room, 2.4 m high, needs about 5,960 BTU/h (1,750 W).
How do I convert watts to BTU?
Multiply the watts by 3.412 for BTU per hour, or divide the BTU/h by 3.412 for watts. A 1,000 W radiator gives 3,412 BTU/h; 6,000 BTU/h is 1,760 W.
What does ΔT50 mean on a radiator?
The output when the water in the radiator is 50 °C warmer than the room (about 70 °C water in a 20 °C room), how radiators are rated. A heat pump runs cooler, nearer ΔT30, where the same radiator gives only about 51% of it.
What size radiator for a bedroom?
A 3.5 × 3 m bedroom, 2.4 m high, kept at 18 °C in an averagely insulated home, needs about 1,010 W (3,440 BTU/h) at ΔT50 on a boiler, or a radiator rated about 1,960 W at ΔT50 on a heat pump.
How accurate is a BTU calculator?
Close enough to pick a radiator for one room in a typical home. It does not know your walls, windows, floors or the weather where you are: for a new system or a heat pump, do a full room-by-room heat loss calculation (EN 12831), or have it done.