Voltage drop calculator

The volts a copper cable loses over its run: see the voltage fall from the board to the load, the drop against 3 and 5%, and the smallest cable size that keeps within.

Your run, board to load
Board230.0 V20 A →20.0 mAt the load222.9 VDrop3%5%3.08%

Copper cable, in section (mm²)

11.52.5▲ smallest46101625
Pick a cable size and watch the far end.

Job sheet

Voltage drop calculator
Voltage drop
7.09 V
3.08% of 230 V
Within 5%?
Yes
5% is 11.50 V
Longest run, 2.5 mm²
32.4 m
at 20 A, within 5%
Smallest cable within the limit
2.5 mm²
for the drop only: check the current it carries
Cable drop
17.7 mV/A/m
copper, at 70 °C

Estimates for planning: cable sizes, protection and the installation follow the wiring rules where you work.

The cable

Cable size (copper)
Units
m

As the cable goes, not as the crow flies.

The circuit

Supply
A

The design current.

V

Line to line on three-phase.

Drop allowed

How it works

Every metre of cable has a little resistance, so the voltage at the far end is lower than at the board. The drop grows with the current and the length, and falls with the size of the cable.

  • Drop: mV/A/m × amps × metres ÷ 1,000, in volts.
  • Percentage: the drop ÷ the supply voltage × 100.
  • Longest run: the volts allowed (5% of 230 V is 11.5 V) × 1,000 ÷ (mV/A/m × amps).

A worked example

A 20 m run of 2.5 mm² cable carrying 20 A, single-phase 230 V: 17.7 × 20 × 20 ÷ 1,000 = 7.09 V, or 3.08%: within the 5% limit. Not sure of the current? Work it out with the watts to amps calculator.

Millivolts per amp per metre, copper

CableSingle-phaseThree-phase
1 mm²43.3 mV/A/m37.5 mV/A/m
1.5 mm²29.0 mV/A/m25.1 mV/A/m
2.5 mm²17.7 mV/A/m15.4 mV/A/m
4 mm²11.0 mV/A/m9.6 mV/A/m
6 mm²7.4 mV/A/m6.4 mV/A/m
10 mm²4.4 mV/A/m3.8 mV/A/m
16 mm²2.8 mV/A/m2.4 mV/A/m
25 mm²1.7 mV/A/m1.5 mV/A/m

Questions

How do I calculate voltage drop?

Multiply the cable’s millivolts per amp per metre by the current and the length, and divide by 1,000. 2.5 mm² copper cable drops about 17.7 mV/A/m single-phase, so 20 A over 20 m drops 17.7 × 20 × 20 ÷ 1,000 = 7.09 V, 3.08% of 230 V.

What is the maximum voltage drop allowed?

For an installation fed from the public supply, the usual limits (in IEC 60364 and the wiring rules built on it) are 3% for lighting and 5% for other circuits, from the origin of the installation to the furthest point. Check the rules where you work.

What size cable do I need for 30 metres?

It depends on the current. At 20 A single-phase on 230 V with 5% allowed, 30 m takes 2.5 mm² for the drop; at 32 A it takes 4 mm². The cable must also carry the current where it is installed.

Why does three-phase drop less?

On a single-phase circuit the current goes out and back, so the drop is twice that of one conductor. Between the lines of a balanced three-phase circuit it is √3 times one conductor, about 13% less, and on a voltage that is higher to start with.

Where do the mV/A/m figures come from?

From the resistance of copper conductors (the maximum IEC 60228 allows), at 70 °C, the temperature of a PVC cable at full load. They come out as the tables of the wiring rules. Reactance is left out, which is fair up to 25 mm².